Skip to content
Install Team

EWC BMPlus Zone Board + URD Dampers + DAPC

This SOP defines the required installation, wiring verification, configuration, and commissioning process for a GE Connect system paired with an EWC BMPlus zone controller, EWC URD dampers, and a DAPC static pressure controller.

Keating Kuhn

Keating Kuhn

January 14, 2026

EWC BMPlus Zone Board + URD Dampers + DAPC

SYSTEM OVERVIEW

Control hierarchy:

  1. EWC BMPlus zone controller – decides which zones are calling and issues open/close commands
  2. DAPC – intercepts damper commands to protect static pressure by floating dampers
  3. URD dampers (MA‑ND5 motors) – power open / power close, floating-point

Key concept:

The zone board decides WHO opens/closes. The DAPC decides HOW MUCH they open when static pressure rises.


POWER

  • One dedicated transformer powers both the BMPlus zone board and the DAPC
  • Transformer R and C is ran to the zone board and jumpered to the DAPC
  • DO NOT steal power from the air handler

WIRING – HIGH‑LEVEL FLOW

Mount BMPlus and DAPC near each other

THERMOSTATS → BMPLUS → DAPC → DAMPERS
                 ↑
           HVAC SYSTEM

STEP 1 – HVAC SYSTEM SETUP

Before zoning is enabled:

  • Confirm HVAC commissioning is complete
  • Verify:
    • Correct airflow per tonnage
    • Staging behavior (Y1/Y2 or inverter logic)
    • Blower ramps correctly

Zoning should never be used to “fix” a bad base system.


STEP 2 – BMPLUS SYSTEM CONFIGURATION

DIP SWITCH SETTINGS (TYPICAL HEAT PUMP APPLICATION)

DIPSETTINGPURPOSE
1Gas vs HPVerifying system type
2CONV or DFElectric vs dual fuel logic
3HCUse heat/cool thermostats
4O or BReversing valve type
5TIMERStage delay by time
6ON50% rule enabled
7ONSupply air sensor active
8GASIndoor fan control

After ANY dip switch change, press RESET on BMPlus.


STEP 3 – ZONE BOARD → AIR HANDLER WIRING VERIFICATION

Verify every conductor:

  • R → R (common transformer hot)
  • C → C (shared common)
  • Y1 / Y2 → GE Connect cooling inputs
  • W1 / W2 → Auxiliary / staging logic
  • G → Indoor blower enable

⚠️ Important:

  • Indoor unit airflow staging is controlled by Y calls, not W

STEP 4 – DAMPER WIRING ARCHITECTURE

URD / MA‑ND5 TERMINALS

TerminalFunction
1 (COM)24V Common
4 (PO)Power Open
6 (PC)Power Close

ZONE BOARD → DAPC (INPUT SIDE)

For each zone:

  • BMPlus M4 → DAPC PO (input)
  • BMPlus M6 → DAPC PC (input)
  • BMPlus M1 → DAPC COM (input)

These go to the BOTTOM terminal blocks on the DAPC.


DAPC → DAMPERS (OUTPUT SIDE)

For each zone output:

  • DAPC PO → Damper PO
  • DAPC PC → Damper PC
  • DAPC COM → Damper COM

Multiple dampers on one zone are wired in parallel.


STEP 5 – DAPC POWER & PRESSURE SENSING

  • Power DAPC from same transformer as BMPlus
  • Install pitot tubes:
    • One in supply
    • One in return
  • Connect tubing correctly (Supply → Supply, Return → Return)

Incorrect tubing = false static readings.


STEP 6 – PRE‑COMMISSIONING CHECK

Before powering up:

  • All zones calling same mode
  • All dampers visually open
  • GE Connect running at max airflow
  • No zone satisfied

If this fails, STOP and fix wiring.


STEP 7 – DAPC MENU SETTINGS (BASELINE)

SettingValue
Target SPFactory (0.5″ wc) initially
Response Delay1 sec
Close Delay30 sec
Damper TypeDefault is Linear – Change to Round or Square
Stroke Time35s (URD default)

Floating Rules

  • Allow largest zones to float
  • Do NOT float small zones
  • Never float fresh air dampers

STEP 8 – DAPC COMMISSIONING

  1. Force all zones calling
  2. Navigate to Commission = YES
  3. Observe dampers:
    • Open
    • Close
    • Float
  4. DAPC discovers non‑zoned static pressure
  5. New SP setpoint is stored automatically

If commissioning fails:

  • DAPC defaults to 0.5″ wc
  • Fix wiring and retry

STEP 9 – FINAL FUNCTIONAL VERIFICATION

Test each zone individually:

  • Single zone call
  • Observe:
    • Other zones closing
    • DAPC floating large zones
    • Static pressure stabilized

Confirm:

  • No duct noise
  • No damper chatter
  • No rapid staging

FAILURE MODES TO WATCH FOR

SymptomLikely Cause
Zones never fully openDAPC wired backwards
High staticCommission skipped
Dampers fightMixed PO/PC wiring
Erratic behaviorTransformer undersized